Vortex (Please call for price)
Overview
Vortex is available in four formats: Wall mounted (Vortex) 19″ rack mounted (Vortex rack) Panel mounted (Vortex panel) or Exd Flameproof (Vortex FP)
Vortex Rack & Panel comprise just the essential input, output and controller modules mounted on a DIN rail. An optional display module is available in panel-mounting and 19″ Rack formats. This configuration is ideal for incorporation into a variety of specialist enclosures, such as 19″ format or those with high ingress protection. Other standard features include RS-485 Modbus communications for remote non-intrusive calibration and configuration.
Channels and display
1 to 12 channels (including 3 for fire) – up to 12 devices can be monitored by reviewing just one control panel, saving time and manpower
Each channel has 1 fault level and 3 alarm levels which can be combined in any pattern to trigger up to 32 output relays – flexibility built in, initially configured to suit your operational needs, then channels/alarms are easily customised by you if requirements change
Can be factory set to your requirements. Then when in situ, can easily be configured to suit your needs using PanelsPro software
Push buttons on front display – day-to-day operations are easily undertaken
LED display panel lights – faults are easily seen and whole system can be checked at a glance
Installation and maintenance
Modbus compatability – no extensive cabling required; cable connections within the unit are easy
Space within units for access to cable terminals
Uses industry standard communication links – simple to integrate into existing control systems
Any adjustments are performed electronically – minimal maintenance and no drift from adjustable potentiometers
Separate zones can be individually inhibited – you can work on specific areas without affecting the rest of the system
Modular construction – replacement parts if required, which plug straight in
Compliance and reliability
Validated to IEC 61508 (SIL 1) – demonstrates system dependability
System monitors relays continuously – coil faults are identified immediately without input from you
Internal battery pack* – power outs are not a problem. Internal battery pack continuously monitored for change levels and connection. System is operational at all times
*Not available on flameproof versions
Specifications
Specifications
Vortex
Vortex Rack/Panel
Size
470 x 306 x 170mm (18.5 x 12 x 6.5 ins)
Rack display: standard 19” 3U Panel display: 441 x 128mm (cut-out 366 x 84.5mm) Modules, PSU and batteries are supplied separately for fitting within a cabinet.
Weight
12Kg (27lbs)
Dependant on configuration
Enclosure material
Back-box: Aluminium Front cover: ABS
Not applicable
Ingress protection
IP66
Cabinet dependent
Channels
Up to 12 (1 to 3 4-way input modules)
Operating temperature
-10°C to +40°C (14°F to +140°F)
Humidity
0-95% RH non-condensing
Inputs
Gas 2 or 3 wire 4-20mA (sink or source), 0-5V
Fire – smoke & heat detectors, manual call-points Up to 3 loops, Up to 20 devices per loop
Outputs
External audible/visual alarm drive Via relays, four 24Vdc 0.5A supplies provided.
Relays
Type Up to 24 SPCO, contacts rated 6A @ 250Vac (1 to 3 8-way relay modules)
Up to 32 SPCO with bus extension module
Assignment – Common Mains fail, battery low and fail
Assignment – Voting Alarms, faults and system events
Relay modes Energised/de-energised, latched/non-latched, time-delayed, pulsed
Digital communications
DCS/PLC/PC: RS-485 Modbus or Profibus Local configuration link: RS-232 (configuration software and lead supplied)
Event logging
Up to 300 alarm, power, fault, system events are stored in Non-Volatile Memory
Panel indication
Channel number: 2-digit 7-segment Green LED Gas reading: 4-digit 7-segment Red LED Measurement units: % LEL, ppm, % Vol, Fire Power: Green LED Battery OK: Green LED Run/hold indication: Green LED Channel test mode: Flashing Amber LED System fault – integrity watchdog: Amber LED
Alarm indication
Audible – internal sounder: Piezo Visual – Alarm: Level 1 & 2, Red LED; Fault – Per channel, Amber LED; Inhibit – Per zone, Amber LED
Power
AC mains: 110/120V & 220/240Vac (switchable) 50-60hz 3.2A max DC: 20-30Vdc Battery back-ip: 2Ah internal
Approvals
Low voltage directive: EN61010-1 EMC: Directive 2014/30/EU: EN50270, FCC: CRF47 Part 15, ICES-003 ATEX: Ex II 2G D Zone 1, Zone 2, IECEx optional
Functional safety
Validated to IEC61508 (SIL1)
Delivery & Returns
Information on delivery and returns can be found on our Delivery and Returns Policy page.