top of page

XgardIQ (Please call for price)

Overview

XgardIQ is an intelligent and versatile fixed detector and transmitter compatible with Crowcon’s full range of sensor technologies. Available fitted with a variety of sensors for fixed flammable, toxic, oxygen or H2S gas detection.

Providing analogue 4-20mA and RS-485 Modbus signals as standard, XgardIQ is optionally available with Alarm and Fault relays and HART communications. The 316 stainless steel are available with three M20 or 1/2“NPT cable entries.

(SIL-2) Safety integrity level 2 certified fixed detector.

Easy and safe to use

  • OLED Display – Bright, clear display indicates gas level and detector status even in dark locations
  • Non-Intrusive Calibration – Zero and calibration functions are performed via the display and keypad, without the need for a hot-work permit or any special tools (e.g. no magnetic wand required)
  • +Ve Safety Indicator – Confirms the detector is operating safely at a glance
  • Event Log Function – Stores all alarm, fault and maintenance events to provide a history of detector use
  • Remote Sensor – Improves probability of detection

Simple installation and maintenance

  • Universal Transmitter – Common transmitter for Crowcon’s full range of sensor technologies
  • Hot-Swap Sensor Modules – Sensors can easily be replaced using one hand without requiring tools or a hot-work permit
  • Auto-Sense Function – Automatically detects whether the control system is 4-20mA current sink or source and sets itself appropriately, eliminating the risk of being incorrectly set
  • Auto-Configure Function – Detects when a sensor module is plugged-in and uploads the appropriate gas type, range, units and alarm levels

Reliability

  • Smart Bump And Speedy Bump Test Functions – Enable sensor health and response to be verified quickly and easily using test gas. Process is automated and provides a reminder when a bump test is due
  • Calibration Due Warning – Reminds the user when calibration is due to ensure that sensors remain operational and accurate at all times
  • Sensor Range Selection – User can set the full-scale range of the sensor via the display menu according to site or specific location requirements.
  • Specifications

    Specifications

    Size H278 x W140 x D89mm (10.9 x 5.5 x 3.5 in)
    Weight 4.1Kg (9lbs)
    Enclosure material 316 stainless steel
    Ingress protection IP66
    Connection Three M20 or ½”NPT cable gland entries.Certified, removable plugs are fitted to left-hand and lower righthand entries
    Power 14-30 VDC. <4W
    Display Main display – OLED 128 x 64 pixels, yellow text on black background
    Indicators – Amber, Red and Green LED’s for detector status; Blue +ve Safety LED
    Electrical output 4-20mA current sink or source (Auto-Sense or manual selection); warning and fault signals are configurable. NAMUR NE 43 compliant
    RS-485 Modbus RTU
    HART 7 over 4-20mA signal and via local I.S. test points (optional)
    Relays (optional)
    Alarm 1, Alarm 2, Fault
    SPCO contacts rated 5A, 230Vac
    Relay configuration options
    Energised or de-energised
    Latching or non-latching
    Rising or falling
    Configurable On and Off delays on alarm relays.
    Event logging Records alarm, fault and maintenance events. Events can be viewed on-screen and downloaded to a PC.
    Operating temperature Transmitter only: -40°C to +75°C (-40°F to +167°F)†

     

    Sensor type:

    Oxygen: (-20°C to +50°C ambient)
    Toxic: (-40°C to +50°C ambient)
    Pellister: (-40°C to +75°C ambient)
    Infra-red (IR): (-20°C to +55°C ambient)
    High temperature toxic:  (-40⁰C to +70⁰C)

    Humidity 0 to 95% RH non-condensing†
    Repeatability +/- 2% FSD
    Zero drift +/- 2% FSD per year maximum
    Response time Sensor dependant: contact Crowcon for specific sensor data.
    Approvals ATEX and IECEx:
    Ex II 2 G    Ex db ia IIC T4 Gb (see above for temperature ranges)
    Performance Designed for compliance with:
    EN50104 (oxygen sensors)
    EN45544 (toxic gas sensors)*
    EN50271 (software)
    H2S performance standard
    Functional safety IEC61508, EN50402 SIL 2
    EMC Compliance EN50270:2015
    FCC CFR47 Part 15B
    ICES-003

    † Note: sensor operating temperature and humidity limits vary widely.

    * Features outstanding at the time of issue, contact Crowcon for details.

    Gases and Ranges

    Gas Units Max
    Range
    Standard
    Range
    Alarm 1
    level
    Alarm 2
    level
    Temp
    range °C 
    Oxygen (O2) %Vol 30 25 19 (falling) 17 (falling) -20 to +50
    Ammonia PPM 100/1000 50 25 35 -20 to +40
     Carbon Monoxide (CO) PPM 1000 250 30 200  -30 to +50
    Hydrogen Fluoride (HF) PPM 10 10 1.8 3 +5 to +40
    Hydrogen Sulphide (H2S) PPM 100/200 25 5 10 -30 to +50
    High Temperature Hydrogen Sulphide (H2S) PPM 100/200 25 5 10 -40 to +70
    Ozone (O3) PPM 1 1 0.1 0.2 -20 to +40
    Sulphur Dioxide (SO2) PPM 100 10 1 1 -30 to +50
    Hydrogen (H2) %LEL 100 100 20 40 -40 to +75
    Methane (CH4) %LEL 100 100 20 40 -40 to +75
    Pentane (C5H12) %LEL 100 100 20 40 -40 to +75
    Propane (C3H8) %LEL 100 100 20 40 -40 to +75
    Ethanol (IR sensor) %LEL 100 100 20 40 -20 to +55
    LPG (IR sensor) %LEL 100 100 20 40 -20 to +55
    Methane (IR sensor) %LEL 100 100 20 40 -20 to +55
    Propane (IR sensor) %LEL 100 100 20 40 +10 to + 55
  • Delivery & Returns

    Information on delivery and returns can be found on our Delivery and Returns Policy page.

£0.00Price